OUTDOOR AIRFLOW CONTROLLER

OAC-3000s-DI

Outdoor Airflow Controller with Network Control Connection for MP-Bus Actuators

The OAC-3000S-DI features a duct insertion mount probe and modulates an MP-Bus damper actuator to maintain precise outdoor airflow. It can operate on a schedule or combine the schedule with a binary input trigger, typically provided by a thermostat or 24 VAC control signal. With advanced logic and airflow measurement, it optimizes CO2,-DCV by adjusting airflow between user-defined limits to maintain a fixed CO2 level or variable setpoint based on occupancy. Fully compatible with MS/TP BACnet systems, the OAC-3000S supports read/write privileges and offers an optional RS-485 signal isolator for isolated networks.

FEATURES

Specifications

FUNCTIONALITY

Outdoor Air Control (OAC) Modes Supported

FLOW: Maintains a user defined airflow setpoint

CO2: Maintains a user defined CO2 level by resetting the outdoor airflow setpoint (requires a CO2 sensor)

CO2/OAF: Maintains a calculated outdoor airflow setpoint based on the estimated ventilation zone population (requires a CO2 sensor)

COUNT: Maintains a calculated outdoor airflow setpoint based on the occupancy counter population (requires an occupancy counter)

FIXED: Maintains a fixed damper position (no control)

Unoccupied Air Control (UAC) Mode Option: Yes, maintains a user defined airflow setpoint

Notification Alarms

“Unoccupied Mode” High/Low Airflow Alarm

“Outdoor Airflow Mode” High/Low Airflow Alarm

“All Modes” CO2 Alarm (requires a CO2 sensor)

“All Modes” System Trouble Alarm

Note: Alarms can be assigned to the contact closure relay

Built-in RTC Scheduler Modes:

Off: No schedule set

Days: Allows a different occupied start time and duration for each day of the week

Weeks: Allows a different occupied start time and duration for weekdays and weekends

USER INTERFACE

Display: 16-character alpha-numeric LCD

Navigation: 4-button interface

BINARY INPUT

BI

Type: Binary Input (BI1)

Assignment: Mode activation trigger signal

Configurable Ranges: 0-24VAC or 0-24VDC

Trigger Threshold

VAC configuration: 6.5 VAC

VDC configuration: 8 VDC

MP-BUS OUTPUT

MP1

Assignment: MP-Bus proportional actuator network signal (requires MP-bus cable, sold separately)

CONTACT CLOSURE RELAY

R1

Type: Dry contact w/ onboard jumper to drive a remote LED

Assignment: OAC alarms or Control Mode

Status: Normally Open (N.O.)

Rating: 30 VDC or 24 VAC @ 3 amp. max.

NETWORK CONNECTIONS

N1

Type: Non-isolated MS/TP BACnet master connection (provide an RS-485 network isolator if isolation is required)

B.A.S. Object Read/Write Access: Yes

Device Load: 1/8 load

Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud

MS/TP BACnet CO2 Sensor Capability: One GreenTrol Automation or approved third-party space mounted or return air CO2 sensor

MS/TP BACnet Occupancy Counter Capability: One to four GreenTrol Automation or approved third-party occupancy counterssensor

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]

Humidity: 5 to 95%

Important: Provide a weather-proof enclosure if the controller module is mounted outdoors

Power Requirement: 24 VAC (22.8 to 26.4 under load) @8.5V-A

Dimensions: 4.34H x 6.59W x 1.83D in. [110.2 x 167.3 x 46.6 mm]

PROBE FUNCTIONALITY

Airflow Measurement: Provides individual sensor node airflow rates to compatible GreenTrol transmitters and controllers

Temperature Measurement: Provides individual sensor node temperatures to compatible GreenTrol transmitters and controllers

AIRFLOW/TEMPERATURE MEASUREMENT PROBE

Type: -UI Universal Insertion Mount Thermal Dispersion Airflow and Temperature Measurement Probe

Available Configurations

Single: 1 probe x 1 sensor node

Dual: 2 probe x 1 sensor nodes

Sensing Node Sensors

Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Probe Tube

Material: Mill finish 6063 aluminum

Probe Mounting Brackets

Material: 304 stainless steel

Probe Length: 6, 8 or 16 in. [152.4, 203.2 or406.4 mm] (adjustable)

Sensing Node Housing

Material: Glass-filled Polypropylene

Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring

Sensing Node Internal Wiring: Kynar® coated copper

Probe to Transmitter Cables

Material: FEP jacket, plenum rated CMP/FT6/CL2P, UL/cUL listed, -67 to 392 ⁰F [-55 to 200 ⁰C], UV tolerant

Standard Lengths: 10, 25 and 50 ft. [ 3.1, 7.6 and 15.2 m]

Connecting Plug: 0.60” [15.24 mm] nominal diameter

Airflow Measurement

Averaging Method: Independent, arithmetic average

Installed Accuracy: Better than ±4% of reading to NIST traceable airflow standards

Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]

Calibration Points: 7

Temperature Measurement

Averaging Method: Independent, velocity weighted

Accuracy: ±0.15⁰F [0.08 ⁰C]

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 160 ⁰F [-28.9 to 48.9 ⁰C]

Note: Temperature limits for operation may be limited by the transmitter or controller selected

Humidity: 0 to 100%