Contact Us Today!     1-877-446-8765

Replacements

IAT-UI

Universal Insertion Mount Thermal Dispersion Airflow and Temperature Measurement

The IAT-UI integrated probe is compatible with GF Series remote transmitters and various GreenTrol application-specific controllers. It is designed for insertion into ducts or other air paths and is available with a 3, 10, 25, or 50-foot plenum-rated cable with connector plug. The probe is available in aluminum only. A universal, adjustable-length tube is available in 6, 8, and 16-inch probe lengths. It is applicable for ducts or other openings up to 8 sq ft.

FEATURES

Specifications

PROBE FUNCTIONALITY

Airflow Measurement: Provides individual sensor node airflow rates to compatible GreenTrol transmitters and controllers

Temperature Measurement: Provides individual sensor node temperatures to compatible GreenTrol transmitters and controllers

AIRFLOW/TEMPERATURE MEASUREMENT PROBE

Type: -UI Universal Insertion Mount Thermal Dispersion Airflow and Temperature Measurement Probe

Available Configurations

Single: 1 probe x 1 sensor node

Dual: 2 probe x 1 sensor nodes

Sensing Node Sensors

Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Probe Tube

Material: Mill finish 6063 aluminum

Probe Mounting Brackets

Material: 304 stainless steel

Probe Length: 6, 8 or 16 in. [152.4, 203.2 or406.4 mm] (adjustable)

Sensing Node Housing

Material: Glass-filled Polypropylene

Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring

Sensing Node Internal Wiring: Kynar® coated copper

Probe to Transmitter Cables

Material: FEP jacket, plenum rated CMP/FT6/CL2P, UL/cUL listed, -67 to 392 ⁰F [-55 to 200 ⁰C], UV tolerant

Standard Lengths: 10, 25 and 50 ft. [ 3.1, 7.6 and 15.2 m]

Connecting Plug: 0.60” [15.24 mm] nominal diameter

Airflow Measurement

Averaging Method: Independent, arithmetic average

Installed Accuracy: Better than ±4% of reading to NIST traceable airflow standards

Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]

Calibration Points: 7

Temperature Measurement

Averaging Method: Independent, velocity weighted

Accuracy: ±0.15⁰F [0.08 ⁰C]

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 160 ⁰F [-28.9 to 48.9 ⁰C]

Note: Temperature limits for operation may be limited by the transmitter or controller selected

Humidity: 0 to 100%

RELATED DOCUMENTATION