Duct Insertion Mount Thermal Dispersion Airflow/Temperature Measurement

The IAT-DI integrated probe is compatible with GF Series remote transmitters and GreenTrol application-specific controllers. The probe is designed for duct insertion into small round ducts (4 to 16 inches) and is available with a 3, 10, 25, or 50-foot plenum-rated cable with a connector plug. Available in aluminum or stainless steel.

The IAT-DI sensor probe uses the principle of thermal dispersion to determine the airflow rate. Thermal dispersion is ideal for HVAC applications that typically require measurement of low air velocities. Each sensing node uses two thermistors to determine airflow. One thermistor is self-heated above ambient, while a second thermistor determines the ambient air temperature. The power dissipated into the airstream is directly related to the airflow rate.

FEATURES

Specifications

PROBE FUNCTIONALITY

Airflow Measurement: Provides individual sensor node airflow rates to compatible GreenTrol transmitters and controllers

Temperature Measurement: Provides individual sensor node temperatures to compatible GreenTrol transmitters and controllers

AIRFLOW/TEMPERATURE MEASUREMENT PROBE

Type: -DI Duct Insertion Thermal Dispersion Airflow and Temperature Measurement Probe

Available Configurations

4 inch [102 mm]: 1 probe x 1 sensor node

5 to 16 inch [127 to 406 mm]: 2 probe x 1 sensor nodes

Sensing Node Sensors

Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Probe Tube

Material: Mill finish 6063 aluminum (optional: 316 SS)

Probe Mounting Brackets

Material: 304 stainless steel

Probe Length: 6, 8 or 16 in. [152.4, 203.2 or406.4 mm] (adjustable)

Sensing Node Housing

Material: Glass-filled Polypropylene

Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring

Sensing Node Internal Wiring: Kynar® coated copper

Probe to Transmitter Cables

Material: FEP jacket, plenum rated CMP/FT6/CL2P, UL/cUL listed, -67 to 392 ⁰F [-55 to 200 ⁰C], UV tolerant

Standard Lengths: 10, 25 and 50 ft. [ 3.1, 7.6 and 15.2 m]

Connecting Plug: 0.60” [15.24 mm] nominal diameter

Airflow Measurement

Averaging Method: Independent, arithmetic average

Installed Accuracy: Better than ±4% of reading to NIST traceable airflow standards

Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]

Calibration Points: 7

Temperature Measurement

Averaging Method: Independent, velocity weighted

Accuracy: ±0.15⁰F [0.08 ⁰C]

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 160 ⁰F [-28.9 to 48.9 ⁰C]

Note: Temperature limits for operation may be limited by the transmitter or controller selected

Humidity: 0 to 100%