Small Ducts & Rooftop Units

GS-N100-D

Airflow and Temperature Measurement System with BACnet MS/TP or Modbus RTU

The GS-N100-D is a high-performance CO2 sensor for today’s demanding DCV applications. It uses Telaire’s NDIR sensing technology and GreenTrol’s high-performance signal processing circuitry. A pitot tube pickup probe that easily inserts into the side of the duct. The pickup probe is typically installed in the return air duct near the air handler for single-zone applications or in the return duct of individual spaces for multi-zone applications. The GS-N100-D time-tested and reliable BACnet MS/TP and Modbus RTU firmware is superior to competitive CO2 sensors. Its reliability makes it the only approved network duct-mounted CO2 sensor for GreenTrol outdoor air controllers. When combined with a GreenTrol outdoor air controller, this CO2 sensor can improve traditional CO2 demand control ventilation by using a unique control algorithm that resets the outdoor air setpoint between user defined upper and lower airflow limits (not damper positions) to maintain the space CO2 level. This eliminates the under- and over-ventilation that is prevalent with traditional CO2-DCV.

FEATURES

Specifications

FUNCTIONALITY

CO2 Measurement: Provides the CO2 level in ppm via the network connection

System Status Alarm: Yes

USER INTERFACE

Baud Rate, Protocol and Addressing: DIP switch

End of Line Termination: Jumper

Important: Modification of the factory default settings requires that power is cycled to the device. It is recommended that each device is bench configured prior to installation OR settings are provided at the time of order so that the device can be factory configured prior to shipment.

CO₂ SENSOR

Technology: Telaire Non Dispersive Infrared (NDIR)

Range: 400 to 2,000 ppm

Sampling Method: Duct mounted pitot tube provided with two 3 foot tubes and inline filter

Required Duct Velocity: 300 to 1,500 FPM [1.52 to 7.62 m/s]

Accuracy: 400 to 1,250 ppm ±30 ppm or 3% of reading, whichever is greater 1,250 to 2,000 ppm ±5% of reading + 30 ppm

Temperature Dependence: 0.36% FS/°F [0.2% FS/°C]

Pressure Dependence: 0.33% of reading per 0.1 in. [2.54 mm] Hg

Stability: <2% of FS over life of sensor (15 year typical)

Calibration Interval: Not required when ABC logic is enabled

Response Time: <2 minutes for 90% step change typical

Signal Update: Every 4 seconds

Warmup Time: 2 minutes operational, 10 minutes to achieve maximum accuracy

TEMPERATURE SENSOR

Technology: Integral Bandgap PTAT

Range: 32 to 122 ⁰F [0 to 50 °C]

Accuracy: ±1.08 ⁰F [0.6 °C] @77 ⁰F [25 °C]

Temperature Dependence: 0.36% FS/°F [0.2% FS/°C]

Pressure Dependence: 0.33% of reading per 0.1 in. [2.54 mm] Hg

Resolution: 0.36 ⁰F [0.2 °C]

Calibration Interval: Not required when ABC logic in enabled

Response Time: <2 minutes for 90% step change typical

Signal Update: Every 4 seconds

Warmup Time: 2 minutes operational, 10 minutes to achieve maximum accuracy

NETWORK CONNECTIONS

N1

Type: Non-Isolated, field selectable MS/TP BACnet master or Modbus RTU connection (provide separate transformer to each GSN100-D or an RS-485 network isolator if isolation is required)

B.A.S. Object/Register Read/Write Access: Yes

Device Load: 1/8 load

Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: 32 to 122 ⁰F [0 to 50 ⁰C]

Humidity: 5 to 95%

Power Requirement: 24 VAC (22.8 to 26.4 under load) @1.5V-A

Dimensions: 6.01H x 3.57W x 1.58D in. [152.6 x 90.7 x 40.1 mm]

Pitot Tube Length: 5.4 in. [137.2 mm