GF-N1000-DI

Airflow and Temperature Measurement System with BACnet MS/TP or Modbus RTU

The GF-N1000-DI is a cost-effective, high-performing duct insertion airflow and temperature measurement device for round ducts. It features two thermal dispersion sensors (probe sizes 5″ to 16″ (one sensor 4″)) with an integral transmitter, delivering precise and reliable airflow readings. Each sensing node is individually calibrated at 7 points in high-performance wind tunnels. The transmitter processes each individual sensor node independently. The result is the true average airflow rate when more than one sensing node is applied. BAS connection is via RS-485 field selectable BACnet MS/TP or Modbus RTU. Installed airflow accuracy is ±4% of reading to NIST traceable standards when installed in accordance with published placement guidelines.

FEATURES

Specifications

FUNCTIONALITY

Airflow Measurement: Provides the average airflow rate in FPM [m/s] to analog output AO1.

Temperature Measurement: Provides the velocity weighted temperature in ⁰F [ ⁰C] to analog output AO2

USER INTERFACE

Output Scaling: Set by DIP switch

AIRFLOW/TEMPERATURE MEASUREMENT PROBE

Type: -DI Duct Insertion Thermal Dispersion Airflow and Temperature Measurement Probe

Available Configurations

4 inch [102 mm]: 1 probe x 1 sensor node

5 to 16 inch [127 to 406 mm]: 1 probe x 2 sensor nodes

Sensing Node Sensors

Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Probe Tube

Material: Mill finish 6063 aluminum (optional: 316 SS)

Probe Mounting Brackets

Material: 304 stainless steel

Probe Mounting: Insertion

Sensing Node Housing

Material: Glass-filled Polypropylene

Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring

Material: Kynar® coated copper

Airflow Measurement

Averaging Method: Independent, arithmetic average

Installed Accuracy: Better than ±4% of reading to NIST traceable airflow standards

Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]

Calibration Points: 7

Temperature Measurement

Averaging Method: Independent, velocity weighted

Accuracy: ±0.15⁰F [0.08 ⁰C]

ANALOG OUTPUT

AO1

Assignment: Linear airflow output signal or equivalent velocity pressure

Configurable Ranges: 0-5V/1-5V or 0-10V/2-10V- specify at time of order

AO2

Assignment: Temperature output signal

Configurable Ranges: 0-5V/1-5V or 0-10V/2-10V– must be same as AO1

Note: The VDC output circuit can drive the input circuit of devices designed to measure 4-wire, 4-20mA, current loops with a resistive load ≥250 ohms

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]

Humidity: 5 to 95%

Important: Not recommended for outdoor use

Power Requirement: 24 VAC (22.8 to 26.4 under load) @5V-A