GF-A2000

Analog Output Airflow/Temperature Transmitter Module w/Contact Closure Airflow Alarm

Transmitter Module w/Contact Closure Airflow Alarm

The GF-A2000 transmitter accepts one IAT-DI probe or up to two IAT-UI/US probes. The transmitter has two analog output signals. One output signal can be assigned to the average airflow of the connected probes or the airflow of the individual probe connected to “P1” when two IAT-UI/DI probes are used. The second output signal can be assigned to the probe connected to “P2” or the average temperature of the connected probes. A contact closure relay is also provided that can be assigned to one or more of the built-in alarms.

FEATURES

Specifications

FUNCTIONALITY

Airflow Measurement: Provides the average airflow rate in FPM [m/s] or CFM [LPS] on the LCD and to analog output AO1 and optionally AO2 when two probes are provided

Configurable Ranges: 0-5V/1-5V or 0-10V/2-10V- specify at time of order

Temperature Measurement: Provides the velocity weighted or arithmetic average temperature in ⁰F [ ⁰C] on the LCD and to analog output AO2 when AO2 is assigned to temperature

Notification Alarms

High/Low Airflow Alarm

System Trouble Alarm

Note: Alarms can be assigned to the contact closure relay or analog output AO2

USER INTERFACE

Display: 16-character alpha-numeric LCD

Navigation: 4-button interface

INTEGRATED SENSOR CAPABILITY

Type: Accepts GreenTrol IAT-DI, IAT-UI and IAT-US Thermal Dispersion Airflow and Temperature Measurement Probe (required). See appropriate IAT product data sheet for probe information.

Available Configurations: IAT-DI Probes

Single Probe: 1 probe x 1 sensor node/probe

Dual Probe: 2 probes x 1 sensor node/probe

ANALOG OUTPUTS

AO1

Assignment: Average airflow output signal of connected probes (P1 and/or P2) or P1 if AO2 is assigned to P2

Configurable Ranges: A0-5V, 0-10V or 2-10V

AO2

Assignment: Airflow output signal of P2, average temperature output signal of connected probes or notification alarm

Configurable Ranges: A0-5V, 0-10V or 2-10V

Note: The VDC output circuit can drive the input circuit of devices designed to measure 4-wire, 4-20 mA, current loops with a resistive load ≥250 ohms

CONTACT CLOSURE RELAY

R1

Type: Dry contact w/ onboard jumper to drive a remote LED

Assignment: Notification alarms

Status: Normally Open (N.O.)

Rating: 30 VDC or 24 VAC @ 3 amp. max

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]

Humidity: 5 to 95%

Important: Provide a weather-proof enclosure if the transmitter module is mounted outdoors

Power Requirement: 24 VAC (22.8 to 26.4 under load) @8.5V-A

Dimensions: 3.57H x 6.00W x 1.50D in. [90.7 x 152.4 x 38.1 mm]