Contact Us Today!     1-877-446-8765

Airflow & Temperature Measurement

GF-A1000-DI

Analog Output Insertion Mount Thermal Dispersion Airflow Measurement.

Device (AMD) for Round Ducts

Thermal Dispersion Airflow/Temperature Measurement Device (ATMD) for Round Ducts

The GF-A1000-DI airflow measurement device is a low cost, high performance, solution for airflow measurement in smaller round ducts. Designed for insertion mounting, the GF-A1000-DI is provided with an integral transmitter. Simply provide 24 VAC/DC power and connect the output cable wires to a BAS or other analog input device to determine the airflow rate. Available in aluminum or stainless steel. Fits 4 to 16 inch round ducts.

FEATURES

Specifications

FUNCTIONALITY

Airflow Measurement: Provides the average airflow rate in FPM [m/s] to analog output AO1.

Temperature Measurement: Provides the velocity weighted temperature in ⁰F [ ⁰C] to analog output AO2

USER INTERFACE

Output Scaling: Set by DIP switch

AIRFLOW/TEMPERATURE MEASUREMENT PROBE

Type: -DI Duct Insertion Thermal Dispersion Airflow and Temperature Measurement Probe

Available Configurations

4 inch [102 mm]: 1 probe x 1 sensor node

5 to 16 inch [127 to 406 mm]: 1 probe x 2 sensor nodes

Sensing Node Sensors

Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Probe Tube

Material: Mill finish 6063 aluminum (optional: 316 SS)

Probe Mounting Brackets

Material: 304 stainless steel

Probe Mounting: Insertion

Sensing Node Housing

Material: Glass-filled Polypropylene

Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring

Material: Kynar® coated copper

Airflow Measurement

Averaging Method: Independent, arithmetic average

Installed Accuracy: Better than ±4% of reading to NIST traceable airflow standards

Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]

Calibration Points: 7

Temperature Measurement

Averaging Method: Independent, velocity weighted

Accuracy: ±0.15⁰F [0.08 ⁰C]

GENERAL PURPOSE INPUT

GP1

Type: Binary Input (BI1)

Assignment: Mode activation trigger signal

Configurable Ranges: 0-24VAC or 0-24VDC

Trigger Threshold:

VAC Configuration: 7 VAC

VAC Configuration: 3 VAC

ANALOG OUTPUT

AO1

Assignment: Linear airflow output signal or equivalent velocity pressure

Configurable Ranges: 0-5V/1-5V or 0-10V/2-10V- specify at time of order

AO2

Assignment: Temperature output signal

Configurable Ranges: 0-5V/1-5V or 0-10V/2-10V– must be same as AO1

Note: The VDC output circuit can drive the input circuit of devices designed to measure 4-wire, 4-20mA, current loops with a resistive load ≥250 ohms

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits & Power Requirements

Environmental Limits

Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]

Humidity: 5 to 95%

Important: Not recommended for outdoor use

Power Requirement: 24 VAC (22.8 to 26.4 under load) @5V-A