Occupancy Counter

GC-N100

Thermal Imaging Occupancy Counter for Interior Doors

The GC-N100 occupancy counter measures the number of people passing through an opening, such as a doorway. It features an RS-485 BACnet MS/TP or Modbus network connection, enabling seamless integration with building automation systems and controllers that support network connectivity. The device utilizes two thermopiles to detect the thermal signatures of individuals passing through the opening in real time.

Designed for applications with ten or more people in a space, the GC-N100 is perfect for population-based demand-controlled ventilation (DCV) applications and is compatible with all GreenTrol outdoor air controllers. Additionally, it is well-suited for general counting applications that analyze occupant movement and activity in settings such as retail and mixed-use spaces. The bi-directional counting capability allows multiple counters to be used within a single area.

FEATURES

Specifications

FUNCTIONALITY

Occupancy Counting: Provides an RS-485 BACnet or Modbus network value for the number of people passing under the counter

USER INTERFACE

Baud Rate, Protocol and Direction: DIP switch

Addressing: DIP switch

End of Line Termination: 2-position switch

Important: Modification of the factory default addressing requires that power is cycled to the device. It is recommended that each device is bench configured prior to installation OR settings are provided at the time of order so that the device can be factory configured prior to shipment.

OCCUPANCY COUNTING SENSOR

Sensors: Two thermopile sensors

Mounting

Standard: Install on the non-swing side of the overhead door jam

Optional: Install above the door frame of either side of the door above with the optional standoff bracket

Accuracy: ±5% or 3 people, whichever is greater

Recommended Maximums for Specified Accuracy

Opening: 42 in. [1.07 m]

Height: 96 in. [2.43 m]

NETWORK CONNECTION

N1

Type: Non-isolated MS/TP BACnet master or Modbus RTUconnection (provide an RS-485 network isolator if isolation is required)

B.A.S. Object Read/Write Access: Yes

Device Load: 1/8 load

Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Recommended Temperature: 65 to 85 ⁰F [18.3 to 29.4 ⁰C]

Humidity: 5 to 95%

Power Requirement: 24 VAC (22.8 to 26.4 under load) @1.5V-A