Contact Us Today!     1-877-446-8765

Replacement Products

GF-N3000

RS-485 BACnet/Modbus Airflow/Temperature Transmitter Module w/Contact Closure Airflow Alarm

The GF-N3000 transmitter is functionally the same as the GF-A2000 with the exception that the BAS connection is via RS-485 field selectable BACnet MS/TP or Modbus RTU. In addition to airflow, temperature and alarm capability, device status is also available via the network.

FEATURES

Specifications

FUNCTIONALITY

Airflow Measurement: Provides the average airflow rate of one or two probes, or optionally of individual probes, in FPM [m/s] or CFM [LPS] on the LCD and via the network.

Temperature Measurement: Provides the velocity weighted or arithmetic average temperature in ⁰F [ ⁰C] on the LCD and to analog output AO2 when AO2 is assigned to temperature.

Notification Alarms

High/Low Airflow Alarm

System Trouble Alarm

Note: Alarms can be assigned to the contact closure relay

USER INTERFACE

Display: 16-character alpha-numeric LCD

Navigation: 4-button interface

INTEGRATED SENSOR CAPABILITY

Type: Accepts GreenTrol IAT-DI, IAT-UI and IAT-US Thermal Dispersion Airflow and Temperature Measurement Probe (required). See appropriate IAT product data sheet for probe information.

Available Configurations: IAT-DI Probes

Single Probe: 1 probe x 1 or 2 sensor nodes/probe

Available Configurations IAT-UI and IAT-US Probes

Single Probe: 1 probe x 1 sensor node/probe

Dual Probe: 2 probes x 1 sensor node/probe

NETWORK CONNECTIONS

N1

Type: Non-isolated, field selectable MS/TP BACnet master or Modbus RTU connection (provide separate transformer to each GFN1000-DI or an RS-485 network isolator if isolation is required)

B.A.S. Object/Register Read/Write Access: Yes

Device Load: 1/8 load

Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud

CONTACT CLOSURE RELAY

R1

Type: Dry contact w/ onboard jumper to drive a remote LED

Assignment: Notification alarms

Status: Normally Open (N.O.)

Rating: 30 VDC or 24 VAC @ 3 amp. max

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]

Humidity: 5 to 95%

Important: Provide a weather-proof enclosure if the transmitter module is mounted outdoors

Power Requirement: 24 VAC (22.8 to 26.4 under load) @8.5V-A

Dimensions: 3.57H x 6.00W x 1.50D in. [90.7 x 152.4 x 38.1 mm]

RELATED DOCUMENTATION