OAC-4000 Controller

Outdoor Airflow Controller Module with Analog Control Output Signal for Proportional Actuators and Analog Input Fan Speed Controllers.

The OAC-4000 modulates a proportional analog actuator or fan speed controller to maintain the outdoor airflow rate. The analog actuator solution allows for larger damper sizes and is ideal for ducted systems to fan coils, makeup air to air handlers, makeup air fans or zone level DOAS applications. DCV requires approved BACnet MS/TP CO2 sensors or occupancy counters.

FEATURES

Specifications

FUNCTIONALITY

Minimum Outdoor Air Control (MOAC) Modes Supported

FLOW: Maintains a user defined airflow setpoint

CO2: Maintains a user defined CO2 level by resetting the outdoor airflow setpoint (requires a CO2 sensor)

CO2/OAF: Maintains a calculated outdoor airflow setpoint based on the estimated ventilation zone population (requires a CO2 sensor)

COUNT: Maintains a calculated outdoor airflow setpoint based on the occupancy counter population (requires an occupancy counter)

FIXED: Maintains a fixed damper position (no control)

PASS: Passes the economizer controller output signal (no control)

Unoccupied Air Control (UAC) Mode Option: Yes, maintains a user defined airflow setpoint

Economizer Controller Fault Signal Output: Not supported

Notification Alarms

“Unoccupied Mode” High/Low Airflow Alarm

“Minimum Outdoor Airflow Mode” High/Low Airflow Alarm

“All Modes” CO2 Alarm (requires a CO2 sensor)

“All Modes” System Trouble Alarm

Note: Alarms can be assigned to the contact closure relay

USER INTERFACE

Display: 16-character alpha-numeric LCD

Navigation: 4-button interface

INTEGRATED SENSOR CAPABILITY

Type: Accepts GreenTrol IAT-DI, IAT-UI and IAT-US Thermal Dispersion Airflow and Temperature Measurement Probe (required unless an external MS/TP airflow measurement device is provided). See appropriate IFT product data sheet for probe information.

Available Configurations: IAT-DI Probes

Single Probe: 1 probe x 1 or 2 sensor nodes/probe

Available Configurations: IAT-UI and IAT-US Probes

Single Probe:Dual Probe: 2 probes x 1 sensor node/probe

Dual Probe: 2 probes x 1 sensor node/probe

GENERAL PURPOSE INPUT

GP1

Type: Binary Input (BI1)

Assignment: Mode activation trigger signal

Configurable Ranges: 0-24VAC or 0-24VDC

Trigger Threshold:

VAC Configuration: 7 VAC

VAC Configuration: 3 VAC

BINARY INPUT

BI

Type: Binary Input (BI1)

Assignment: Mode activation trigger signal

Configurable Ranges: 0-24VAC or 0-24VDC

Trigger Threshold

VAC configuration: 6.5 VAC

VDC configuration: 8 VDC

ANALOG OUTPUT

AO1

Assignment: Airflow control signal

Configurable Ranges: 0-5V, 0-10V, 2-10V, or 4-20mA

Maximum Number of Actuators Supported:

0-5V, 0-10V or 2-10 V: Unlimited

4-20mA: 2

MP-BUS OUTPUT

MP1

Assignment: MP-Bus proportional actuator network signal (requires MP-bus cable, sold separately)

CONTACT CLOSURE RELAY

R1

Type: Dry contact w/ onboard jumper to drive a remote LED

Assignment: OAC alarms or Control Mode

Status: Normally Open (N.O.)

Rating: 30 VDC or 24 VAC @ 3 amp. max.

NETWORK CONNECTIONS

N1

Type: Non-isolated MS/TP BACnet master connection (provide an RS-485 network isolator if isolation is required)

B.A.S. Object Read/Write Access: Yes

Device Load: 1/8 load

Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud

MS/TP BACnet Airflow Sensor Capability: One GreenTrol Automation or approved third-party airflow measurement device (cannot be used if an integrated airflow measurement device is connected).

MS/TP BACnet CO2 Sensor Capability: One GreenTrol Automation or approved third-party space mounted or return air CO2 sensor

MS/TP BACnet Occupancy Counter Capability: One to four GreenTrol Automation or approved third-party occupancy counters sensor

ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS

Environmental Limits

Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]

Humidity: 5 to 95%

Important: Provide a weather-proof enclosure if the controller module is mounted outdoors

Power Requirement: 24 VAC (22.8 to 26.4 under load) @8.5V-A

Dimensions: 4.34H x 6.59W x 1.83D in. [110.2 x 167.3 x 46.6 mm]