The IAT-US integrated probe is compatible with GF Series remote transmitters and various GreenTrol application specific controllers. The probe is designed for insertion into outdoor air intakes, plenums or other air paths and is available with a 3, 10, 25 or 50 foot plenum rated cable with connector plug. Available in aluminum only. Universal, adjustable length tube can be rotated on its mounting bracket. Probes are available in 6, 8 and 16 inch lengths. Applicable for outdoor air intakes, plenums or other openings up to 8 sq ft.
Airflow Measurement: Provides individual sensor node airflow rates to compatible GreenTrol transmitters and controllers
Temperature Measurement: Provides individual sensor node temperatures to compatible GreenTrol transmitters and controllers
Type: -US Universal Insertion Mount Thermal Dispersion Airflow and Temperature Measurement Probe
Available Configurations
Single: 1 probe x 1 sensor node
Dual: 2 probe x 1 sensor nodes
Sensing Node Sensors
Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe
Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe
Probe Tube
Material: Mill finish 6063 aluminum
Probe Mounting Brackets
Material: 304 stainless steel
Probe Length: 6, 8 or 16 in. [152.4, 203.2 or406.4 mm] (adjustable)
Sensing Node Housing
Material: Glass-filled Polypropylene
Sensor Potting Materials: Waterproof marine epoxy
Sensing Node Internal Wiring
Sensing Node Internal Wiring: Kynar® coated copper
Probe to Transmitter Cables
Material: FEP jacket, plenum rated CMP/FT6/CL2P, UL/cUL listed, -67 to 392 ⁰F [-55 to 200 ⁰C], UV tolerant
Standard Lengths: 10, 25 and 50 ft. [ 3.1, 7.6 and 15.2 m]
Connecting Plug: 0.60” [15.24 mm] nominal diameter
Airflow Measurement
Averaging Method: Independent, arithmetic average
Installed Accuracy: Better than ±4% of reading to NIST traceable airflow standards
Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]
Calibration Points: 7
Temperature Measurement
Averaging Method: Independent, velocity weighted
Accuracy: ±0.15⁰F [0.08 ⁰C]
Environmental Limits
Temperature: -20 to 160 ⁰F [-28.9 to 48.9 ⁰C]
Note: Temperature limits for operation may be limited by the transmitter or controller selected
Humidity: 0 to 100%