Description
FEATURES
The GA-200 is a multi-function device. It can be used to display the output of any analog or BACnet MS/TP sensor. The GA-200 can act as network bridge and convert an analog output sensor to a BACnet MS/TP or Modbus RTU sensor. The device has a built-in high, low or high/ low setpoint alarm that can alarm on a physical analog input or BACnet MS/TP AI. The GA-200 can also display the physical analog input or BACnet MS/TP AI on a 16-character LCD with user defined units of measure
OVERVIEW
FUNCTIONALITY
Display: Display the measured analog input, AI1 (or BACnet MS/TP AI1), on the LCD with user defined units of measure
Alarm: Low and/or high user defined setpoint alarm on AI1 with user defined % of setpoint or fixed value tolerance
Delay: User defined
Reset Method: Manual or automatic
Visual Indication: Yes, LCD and red indicating LED
Network Indication: Yes
Contact Closure Relay Assignment: Yes, R1
Network Bridge Capability: Convert AI1 to a BACnet MS/TP AI, AV or AO object or dual register Modbus RTU value (high byte/low byte user definable)
USER INTERFACE
Display: 16-character alpha-numeric LCD
Navigation: 4-button interface
ANALOG INPUT
AI1
Type: Analog Input (AI1)
Assignment: User defined analog signal
Configurable Ranges: 0-10V or 4-20mA (4-wire)
CONTACT CLOSURE RELAY (AI1) ALARM
R1
Type: Dry contact w/ onboard jumper to drive a remote LED
Assignment: Active alarm
Status: Normally Open (N.O.)
Rating: 30 VDC or 24 VAC @ 3 amp. max
NETWORK CONNECTION
N1
Type: Non-isolated MS/TP BACnet master (provide an RS-485 network isolator if isolation is required) or Modbus RTU connection
Protocol: Field selectable
B.A.S. Object Read/Write Access: Yes
Device Load: 1/8 load
Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud
ENVIRONMENTAL LIMITS, POWER REQUIREMENTS & DIMENSIONS
Temperature: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]
Humidity: 5 to 95%
Power Requirement: 24 VAC (22.8 to 26.4 under load) @2.5V-A
Dimensions: 3.57H x 6.00W x 1.58D in. [90.7 x 152.4 x 40.1 mm]