The GS-N100-W is a high-performance CO2 sensor housed in an attractive enclosure designed to meet the demands of modern demand control ventilation (DCV) applications. Engineered with Telaire’s proven NDIR sensing technology and GreenTrol’s advanced signal processing circuitry, the GS-N100-W ensures superior accuracy and reliability. With BACnet MS/TP and Modbus RTU firmware, the GS-N100-W outperforms competitive CO2 sensors, making it the only approved network wall-mounted CO2 sensor for GreenTrol outdoor air controllers.
Baud Rate, Protocol and Addressing: DIP switch
End of Line Termination: Jumper
Important: Modification of the factory default settings requires that power is cycled to the device. It is recommended that each device is bench configured prior to installation OR settings are provided at the time of order so that the device can be factory configured prior to shipment.
Technology: Telaire Non Dispersive Infrared (NDIR)
Range: 0 to 2,000 ppm
Accuracy: 400 to 1,250 ppm ±30 ppm or 3% of reading, whichever is greater
1,250 to 2,000 ppm ±5% of reading + 30 ppm
Temperature Dependence: 0.36% FS/°F [0.2% FS/°C]
Pressure Dependence: 0.33% of reading per 0.1 in. [2.54 mm] Hg
Stability: <2% of FS over life of sensor (15 year typical)
Calibration Interval: Not required when ABC logic in enabled
Response Time: <2 minutes for 90% step change typical
Signal Update: Every 4 seconds
Warmup Time: 2 minutes operational, 10 minutes to achieve maximum accuracy
N1
Type: Non-Isolated, field selectable MS/TP BACnet master or Modbus RTU connection
B.A.S. Object/Register Read/Write Access: Yes
Device Load: 1/8 load
Supported Baud Rates: 9.6, 19.2, 38.4 and 76.8 kbaud
Environmental Limits
Temperature: 32 to 122 ⁰F [0 to 50 ⁰C]
Humidity: 5 to 95%
Power Requirement: 24 VAC (22.8 to 26.4 under load) @1.5V-A
Dimensions: 4.56H x 3.25W x 1.09D in. [115.8 x 82.6 x 27.7 mm]